Solution: Changing the design and replacing one chiller We
converted the primary/secondary loop design to a variable primary design by removing the primary chilled water pumps, and
installing a minimum flow chilled water by-pass to ensure the manufacturers recommended minimum flow to operate chillers.
This prevented the necessity to start the second chiller before the first chiller was operating at 100% capacity. In fact
since we made this retrofit conversion, there hasn’t been a need to run the second chiller and it’s related auxiliary
equipment. As part of this energy retrofit, we replaced one chiller with a Variable Speed Drive (VSD) driven 400-ton
chiller using R-134A refrigerant. We also adjusted the Variable Frequency Drives (VFD’s) to control chilled water pumping
volume, installed VFD’s on the cooling tower fans and set condenser water control point at 55 degrees with a wet-bulb
reset to conserve tower fan energy. The 55 degrees condenser water control point, when conditions allowed, permitted
the new variable speed chiller we installed to operate at efficiently as low as .33Kw Ton.
|